UKOOA LV Power Cable
-
UKOOA Type LA 600/1000V Fire Resistant
Application
These cables are designed for fixed installation for power, control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.
Standards
BS 6883/BS 7917/UKOOA
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2Construction
Conductors Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228. Insulation EPR complying with BS7655 GP4 Bedding EVA - SW4 compound complying with BS 7655. Armour Tinned Phosphor Bronze Wire Braid to BS2873-PB102 (now BS EN 12166) Outer Sheath EVA - SW4 compound complying with BS 7655 Dimensions and Weight
Construction
No. of cores×Cross section(mm²)Nominal Insulation Thickness
mmNominal Thickness of Inner Sheath
mmNominal Thickness of Outer Sheath
mmNominal Overall Diameter
mmApprox. Weight
kg/km1×1.0 0.8 1.1 1.2 9.5 150 1×1.5 0.8 1.1 1.2 9.8 170 1×2.5 0.8 1.1 1.2 10.2 190 1×4 1.0 1.1 1.2 11.3 260 1×6 1.0 1.1 1.2 11.8 340 1×10 1.0 1.1 1.2 13.0 390 1×16 1.0 1.1 1.2 14.2 480 1×25 1.2 1.1 1.2 16.8 565 1×35 1.2 1.1 1.3 17.9 740 1×50 1.4 1.1 1.4 19.7 940 1×70 1.4 1.0 1.4 21.9 1270 1×95 1.6 1.2 1.4 24.5 1500 1×120 1.6 1.4 1.6 26.6 1750 1×150 1.8 1.6 1.8 29.0 2200 1×185 2.0 1.8 2.1 32.6 2700 1×240 2.2 1.3 1.5 36.0 3400 1×300 2.4 1.5 1.7 39.2 4200 1×400 2.6 1.7 2.0 43.7 5700 1×500 2.8 1.2 1.3 48.1 7200 1×630 2.8 1.0 1.2 52.3 8840