UKOOA MV Power Cable
-
UKOOA Type HB 8.7/15kV Flame Retardant
Application
These cables are designed for use in fixed wiring on ships and offshore platforms and drilling rigs, especially used where life may be endangered by smoke and noxious fumes, and where sensitive equipment may be damaged by acid forming gases.
Standards
BS 6883/BS 7917/UKOOA
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2Construction
Conductors Stranded class 2 tinned annealed copper conductors to BS 6360/IEC 60228. Conductor Screen Semi-conductive tape or an extruded layer of semi-conductive compound Insulation EPR complying with BS7655 GP4 Insulation Screen Semi-conductive tape or an extruded layer of semi-conductive compound Metallic Screen Copper Tape Bedding CSP – SW2 or EVA - SW4 compound complying with BS 7655. Armour Galvanised steel wire braid to BS 6883 Outer Sheath CSP – SW2 or EVA - SW4 compound complying with BS 7655. Dimensions and Weight
Construction
No. of cores×Cross section(mm²)Nominal Insulation Thickness
mmNominal Thickness of Inner Sheath
mmNominal Thickness of Outer Sheath
mmNominal Overall Diameter
mmApprox. Weight
kg/km3×25 4.5 2.2 2.5 50.5 3610 3×35 4.5 2.3 2.6 52.9 4510 3×50 4.5 2.4 2.7 55.7 5210 3×70 4.5 2.6 2.9 60.1 6390 3×95 4.5 2.7 3.0 64.6 7660 3×120 4.5 2.9 3.2 68.3 8810 3×150 4.5 3.0 3.3 72.1 10070 3×185 4.5 3.2 3.5 76.7 11420 3×240 4.5 3.4 3.8 86.6 13830 3×300 4.5 3.6 4.0 92.8 16200