UKOOA Instrumentation Cable
-
UKOOA TYPE KH / TYPE KK 150/250V Flame Retardant
Application
These cables are designed for fixed installation for control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.
Standards
BS 6883/BS 7917/UKOOA
IEC 60331-21
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2Construction
Conductors Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228. Insulation EPR complying with BS7655 GP4 Drain Wire Tinned copper drain wire Individual Screen Aluminium mylar tape screen Bedding EVA - SW4 compound complying with BS 7655 Armour Galvanised steel wire braid to BS 6883 Outer Sheath EVA - SW4 compound complying with BS 7655 (TYPE KH: Blue; TYPE KK: Grey). Dimensions and Weight
-
Construction
No. of cores×Cross section(mm²)Nominal Insulation Thickness
mmNominal Thickness of Inner Sheath
mmNominal Thickness of Outer Sheath
mmNominal Overall Diameter
mmApprox. Weight
kg/km1×2×0.75 0.8 1.0 1.2 11.5 230 3×2×0.75 0.8 1.2 1.4 16.5 430 7×2×0.75 0.8 1.4 1.6 21.0 720 12×2×0.75 0.8 1.6 1.8 27.0 1110 1×3×0.75 0.8 1.0 1.2 12.0 245 3×3×0.75 0.8 1.3 1.5 18.5 530 7×3×0.75 0.8 1.5 1.7 23.5 900 12×3×0.75 0.8 1.7 2.0 31.0 1530 1×4×0.75 0.8 1.2 1.3 13.5 310 1×2×1.0 0.8 1.0 1.2 12.0 240 3×2×1.0 0.8 1.3 1.4 17.0 490 1×3×1.0 0.8 1.1 1.2 12.5 285 1×4×1.0 0.8 1.2 1.4 14.0 340 1×2×1.5 0.8 1.1 1.2 12.5 290 3×2×1.5 0.8 1.3 1.5 18.5 560 1×3×1.5 0.8 1.1 1.2 13.0 320 1×4×1.5 0.8 1.2 1.4 14.5 370 20×2×1.5 0.8 2.0 2.3 38.0 2430